{"product_id":"basler-electric-be1-25-79s-solid-state-reclosing-relay","title":"Basler Electric BE1-25 79S Solid State Reclosing Relay","description":"\u003cdiv\u003e\u003cp\u003eBasler Electric BE1-25 79S Sync-Check\/Single Shot Reclosing Relay is a solid‑state protective relay that provides automatic reclosing of a tripped circuit breaker. It operates with the breaker’s Form B auxiliary contact to detect the breaker's position and uses a reclose initiate (RI) signal from the protective system to permit reclosing. A reclose cancel (RC) signal can inhibit automatic reclosing; RC must be present at least 8 milliseconds before it is recognized. After the breaker opens, the RESET indicator goes out and the relay compares sensed line and bus voltages against a minimum voltage limit of 80 Vac; if either voltage falls below this threshold, a preselected reclose timer period is started. If the breaker is still open and RC is not present at the end of the timer, the relay proceeds with a reclose attempt according to the Sync-Check\/Single Shot reclosing logic. The BE1-25\/79S thus combines Sync-Check timing to confirm voltages are suitable before closing in, with a single-shot reclosing sequence intended to restore service after transient faults, making it suitable for integration with Basler Electric protection schemes in transmission and distribution installations.\u003c\/p\u003e\u003c\/div\u003e","brand":"Basler","offers":[{"title":"Used Surplus - Excellent Condition","offer_id":51676723052846,"sku":null,"price":1115.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0940\/0818\/1038\/files\/Ebay_website_image_3216f15b-83c0-4b5a-b304-e16fe2b15ad2.jpg?v=1769552624","url":"https:\/\/plgautomation.com\/products\/basler-electric-be1-25-79s-solid-state-reclosing-relay","provider":"PLG Automation ","version":"1.0","type":"link"}