3-7 Days Delivery Within U.S. - Call/Email For NEXT DAY AIR
📞 800-906-9271 ✉️ sales@plgautomation.com

New

Pepperl+Fuchs KFD2-SR2-EX2.W AMPLIFIER KFD2SR2EX2.W

Includes PLG Automations 1-Year Warranty
Get a Quote Arrow
payment logos
Disclaimer: PLG Automation sells surplus, refurbished, & used items and is not an authorized distributor for the brands listed. Our products come with PLG Automation's 1-year warranty, not the original manufacturer's warranty. Trademarks and brands mentioned belong to their respective owners; the website is not endorsed by any manufacturer.
Learn more

Product Description


The Pepperl+Fuchs KFD2-SR2-EX2.W is a two-channel isolated switch amplifier designed to interface with NAMUR sensors and dry contact switches, converting their signals into relay outputs suitable for control systems. It operates with a 19 to 30 V DC supply voltage and features relay contact outputs capable of handling up to 2 A at 250 V AC or 40 V DC. With an IP20-rated housing, the device is suitable for mounting on a 35 mm DIN rail in industrial environments.



Technical Specifications


  • Signal Type: Digital Input​
  • Pepperl+Fuchs
  • +1
  • Franklin Empire
  • +1
  • Functional Safety: SIL 2 (IEC/EN 61508)​
  • Pepperl+Fuchs
  • Supply Voltage: 19 to 30 V DC​
  • Franklin Empire
  • Supply Current: ≤ 50 mA​
  • Power Dissipation: ≤ 1 W​
  • Franklin Empire
  • Input Connections: Terminals 1+, 2+, 3-; 4+, 5+, 6-​
  • Pepperl+Fuchs
  • Input Characteristics: NAMUR standard (8 V open circuit voltage, 8 mA short-circuit current)​
  • Pepperl+Fuchs
  • Line Fault Detection: Breakage detection (I ≤ 0.1 mA), short-circuit detection (I > 6 mA)​
  • Pepperl+Fuchs
  • Output Connections: Terminals 7, 8, 9 (Output I); 10, 11, 12 (Output II)​
  • Pepperl+Fuchs
  • Relay Contact Ratings: 250 V AC/2 A (cos φ > 0.75); 126.5 V AC/4 A (cos φ > 0.75); 40 V DC/2 A resistive load​
  • Pepperl+Fuchs
  • +1
  • Franklin Empire
  • +1
  • Minimum Switching Current: 2 mA at 24 V DC​
  • Pepperl+Fuchs
  • Switching Frequency: ≤ 10 Hz​
  • Galvanic Isolation: Reinforced insulation (rated voltage 300 V AC) between input, output, and power supply​
  • Pepperl+Fuchs
  • Ambient Temperature Range: -40 to 70 °C (-40 to 158 °F)​
  • Housing: IP20-rated, suitable for DIN rail mounting (35 mm)​
  • Franklin Empire
  • Dimensions: 20 mm (W) x 119 mm (H) x 115 mm (D)​
  • Pepperl+Fuchs
  • Approvals: cULus Listed, FM, IECEx, ATEX
0 Reviews for
Add A Review

You need to login for writing a review. Login to your account

Comments (0)

No Comments found !

Leave Your Comment

You need login for posting a comment. Login to your account

Additional Information

icn
Shipping Information

Free Shipping On All Orders. Most Products Ship From The US And Are Delivered Within 3-7 Days. Contact Phone Support or Sales For Overnight And 2 Day Shipping Options.

icn
Warranty Information

All Products Come With PLG Automation's 1-Year Warranty.

icn
Payment Method

We only accept online payments such as Visa, Mastercard, American Express, Discover, & PayPal. All payments are entirely secured.